ACI
A/1K-LTS-GD-100'

The A/100-LTS, A/1K-LTS, A/TT100-LTS, and A/TT1K-LTS Series sensors and temperature transmitters incorporate a Class B, wire wound platinum RTD sensor which conforms to DIN-IEC-751 and DIN 43760 platinum RTD standards. ACI's cryogenic submersible sensor and transmitter is manufactured using a 1000 ohm platinum RTD. The transmitter produces a linear, 4-20mA output carried on a two-wire system. The transmitter is supplied factory calibrated and is protected from EMI and load resistances of up to 800 ohms. The transmitter's current output can also be limited upon request. The A/100-LTS and A/1K-LTS are submersible sensors without a transmitter. This will provide a 3-wire 100 or 1000 ohm RTD resistive output. One of the most important features of the A/100-LTS, A/1K-LTS, A/TT100-LTS and A/TT1K-LTS is that the 2" Stainless Steel remote probe with 10' or 30’ Teflon leads and is fully submersible. An optional Glycol bottle is available upon request. Please see ordering information for housing options.